Conductivity Controller (0.00 to 19.99 μS/cm) - BL983322

£

Conductivity Controller (0.00 to 19.99 μS/cm) - BL983322

 

Details

BL983322

Adjustable Dry Contact Dosing Relay

The BL983322 features a dosing relay that is activated when the reading is above a user programmable set point.

Programmable Overdose Protection

For enhanced safety the mini controller can be programmed to deactivate the dosing relay if the set point is not reached within a specified time interval. The overdosing timer is programmable from 5 to 30 minutes or disabled.

Relay Control Override

With the flick of a switch the mini controller's relay can be disabled (Off), placed in control (Auto), or be activated for manual operation (On) which is useful for priming a dosing pump.

Multicolor LED Indicator

Multicolor LED indicator allows an operator to quickly check the status of the controller.

  • Green = Meter in measurement mode and reading is below the set point.
  • Orange/Yellow = Reading is above the set point and the relay is activated.
  • Blinking Red = Indicates an alarm condition such as when the maximum dosing time has been exceeded.
BL983322

Fuse Protected Dosing Contacts

The relay dosing contact is rated for up to a 2A load and is fuse protected.

Labeled Termination Connections

Quick-connect terminal blocks are clearly labeled for easy connection to power, conductivity probe and relay that can be used to operate a dosing pump, valve, audible alarm, or light.

HI7634

1/2" NPT Male Threaded Amperometric Probe for Mounting In-line*

The BL983322 mini controller uses the HI7634 conductivity probe that is available with different cable lengths.

*HI7634 is not included and must be ordered separately

 

BL931700

Front View

Installation cut-out dimensions are provided as well as outside panel dimensions.

BL931700

Side View

Adjustable location brackets allow the controller to slide easily and securely into place..

Range 0.00 to 19.99 μS/cm
Resolution 0.01 μS/cm
Accuracy (@25°C/77°F) ±2% f.s.
Calibration manual, with CAL trimmer
Dosing Relay maximum 2A (fuse protected), 250 Vac, 30 VDC
Dosing Selection contact closed when measure > setpoint
Setpoint adjustable from 0 to 19.99 μS/cm
Overtime adjustable, typically from 5 to approximately 30 minutes
Temperature Compensation automatic from 5 to 50°C (41 to 122°F) with β =2%/oC
Power Supply models “-0”: 12 VDC adapter (included)
models “-1”: 115/230 VAC; 50/60Hz
Dimensions 83 x 53 x 99 mm (3.3 x 2.1 x 3.9’’)
Weight models “-0”: 200 g (7.1 oz.) models “-1”: 300 g (10.6 oz.)
Ordering Information BL983322-1 (115/230 VAC) and BL983322-0 (12 VDC) supplied with mounting brackets, transparent cover and instruction manual.

 